HORNER MODULES FOR GE FANUC PLCs - ANALOG OUTPUT
These Series 90-30 modules provide traditional analog output channels but incorporate +/-2000VDC isolation, channel-to-channel and channel-to-ground.

They feature four channels of output, with 14-bit (13-bit plus sign) resolution. Current (4-20mA) and voltage (+/- 10V) models are available. Both modules convert digital values (-32,000 to +32,000) residing in %AQ registers into analog signals. The %AQ values are set by the ladder logic program in the PLC CPU. Each channel may be set to "0" or "hold last state" when the PLC is taken out of RUN mode. This is accomplished with a configuration parameter in the configuration software. The output mode of each channel in the DAC420 may be set to 4-20mA or 0-20mA.
DAC410 DAC420
Number of Channels 4
Output Range +/- 10V 4-20mA or 0-20mA
Channel-to-Channel Isolation 1500VAC (RMS), +/-2000VDC
Common Mode Range 1500VAC (RMS), +/-2000VDC
Useable Resolution 13 bits + sign
Power Consumption 1.23W @ 5V, 4.13W @ 24V 1.23W @ 5V, 3.74W @ 24V
I/O Points Required 4 %AQ
Maximum Linearity Error 0.02% full scale
Operating Temperature 0 to 60°C
Relative Humidity 5% to 95%, non-condensing




 
You need a Flash Player to view this ad. Please go to here to get one.
home | about us | how to buy | manuals | tech support | products | news & brochures | contact