Profibus DP |
HE693PBM100![]() HE693PBS105 HE693PBS106 The Profibus DP network interfaces available from Horner Electric are the only network interfaces available for use with GE Fanuc Series 90-30 PLCs. Both master (HE693PBM100) and slave (HE693PBS105) modules are available. The PBM100 functions as a Profibus DP network master controlling up to 64 slave devices. The PBS105 slave module acknowledges parameters and configurations from a Profibus master and replies with diagnostic information. Profibus DP, a token-passing network, supports one master controlling the network and writing to the slaves, but multiple masters may read information off of the Profibus network. The Profibus DP application allows for the connection of I/O devices and simple field devices to an automation system. Emphasis is on fast transmission of small data volumes. The HE693PBM100 and the HE693PBS105 are available through Horner Electric and our family of authorized distributors. Call you local distributor for pricing and availability. |
PROFIBUS MASTER UPDATES (05/01/00) HE693PBM101 AY - D Requires Windows 95 or 98 HE693PBM100 J - M Requires Windows 95 or 98 HE693PBM100 AX - H Requires Windows 95 or 98 |
| Protocol | Profibus DP |
| Maximum # of Segments | 4 (w/ 3 repeaters) |
| Network Distance | Varies by network speeds and repeaters |
| Network Size | 64 nodes (two 32-node segments with repeaters) |
| Network Type | Master/Slave; Toke passing |
| Data Volume Supported | 240 bytes in / 240 bytes out (per slave) |
| Configuration (PBM100) | Cimplicity Control V2.00 |
| Configuration (PBS100) | |
| CPU Required (Both) | GE Fanuc CPU351 V8.0 (or greater) |
| Baud Rate | Line Lengths |
| 9.6 kbits | 1200 meters |
| 19.2 kbits | 1200 meters |
| 93.75 kbits | 1200 meters |
| 187.5 kbits | 600 meters |
| 500 kbits | 200 meters |
| 1500 kbits | 200 meters |
| 12 megabits | 100 meters |