Horner Electric's isolated relay output modules for the Series 90-30, the RLY100 and 110, provide eight high-current (8A) relay outputs. While outputs on both modules are isolated, the RLY100 offers no fused outputs and the RLY110's outputs are fused. Both modules can handle AC (12-120V, 47-63Hz) or DC (12-30V) loads. Because the outputs are dry contacts, a mixture of voltage types and levels can be used simultaneously. The combination of high current capacity and circuit isolation gives a system designer maximum flexibility. This module eliminates costly isolation relay and wiring cost, further adding to its desirability and cost justification.

 

 

Pricing

Specifications

Manual

Sales Literature

 

RLY100

RLY110

Number of Discrete Outputs

8

I/O Points Required

8 %Q points

Operating Voltage

12-120VAC, 12-30VDC

AC Frequency

47-63Hz

Maximum Current per Output

8A

Maximum Inrush (fuse rating)

200% for 10 seconds

Maximum Total Current

50A

Minimum Recommended Current

10mA @ 12V

Fuses

NA

10A

Contact Types

2 normally open/normally closed, 6 normally open

Operating Temperature

0-60°C

Relative Humidity

5 to 95% (non-condensing)

Internal Power Consumption

50mA @ 5VDC, 150mA @24VDC